A combustion plant is monitored on three levels that overlap only partly. Efficiency depends on the air–fuel ratio, and therefore on the oxygen and carbon monoxide in the flue gas. Safety depends on reliable flame detection. Environmental compliance depends on measuring stack emissions with methods and equipment accepted by the authority. Each level has its own instruments, and confusing them leads either to duplicated investment or to gaps in monitoring.
Key takeaways
- Residual oxygen is the basic variable for combustion control: too much air means stack losses, too little means CO and unburnt fuel.
- In-situ zirconia probes respond quickly and need no sampling system; CO can be measured in-situ by non-dispersive infrared (NDIR).
- The flame detector is a safety device: the UV/IR choice, safety time and SIL level depend on the fuel and the burner.
- CEMS serves compliance: certified analysers, data quality assurance (QAL1, QAL2, QAL3) and validated averages for comparison with permit limits.
Oxygen and excess air
Complete combustion requires air above the stoichiometric amount, but every additional percent of air heats a volume of gas that leaves through the stack for nothing. Excess air can be estimated from the measured oxygen, approximately λ ≈ 20.9 / (20.9 − O₂). At 3 % O₂, λ is about 1.17, i.e. 17 % excess air. If oxygen drops too far, CO rises sharply: unburnt fuel, soot and the risk of deposits appear. The optimum lies just before this rise and depends on the burner, the fuel and the load.
Two practical rules follow. First: the O₂ setpoint must vary with load, because burners need more air at low load. The Ascon Tecnologic OXR trim controller corrects the air flow according to boiler load, with up to 2 curves of 4 segments each. Second: O₂ and CO are read together. Oxygen shows how much excess air there is; CO shows whether combustion is complete. LAMTEC BurnerTronic BT300 burner control systems offer O₂ control and CO/H₂ optimisation as options.
The zirconia probe
The heated zirconia cell generates a signal that depends on the difference between the oxygen partial pressure in the gas and in the reference air. Mounted directly in the duct, it measures the wet gas, without sampling. Ascon Tecnologic ZO2-4 probes measure 0.3 … 25 % O₂, with an accuracy of ±0.5 % of full scale and a response time below 50 ms, in flue gas up to 500 °C. Calibration is done in ambient air, every 12 months, without test gas cylinders. The probe is intended for natural gas plants; for other fuels with low sulphur content, the application is evaluated together with us.
A word of caution on comparisons: extractive analysers usually measure after condensate removal, on a dry basis, so their O₂ reading is higher than that of an in-situ probe on wet gas. The difference is not an error of either instrument.
In-situ or extractive
| Criterion | In-situ analysis | Extractive analysis |
|---|---|---|
| Principle | Sensor or optical path directly in the duct | Gas is sampled, transported and conditioned before analysis |
| Measurement basis | Wet gas, at duct conditions | Usually dry gas, after condensate separation |
| Response time | Very short (ZO2-4: below 50 ms) | Includes transport time along the sample line |
| Maintenance | No sample line; O₂ calibration in air, CO zero without test gas (ZCO) | Filters, sample line, sample conditioning, calibration gases |
| Parameters | O₂, CO, temperature | Wide range: O₂, CO, CO₂, NOx, SO₂, NH₃, TOC and others |
| Examples | Ascon Tecnologic ZO2-4, ZCO, iCOMB range | Ascon Tecnologic eCOMB, CEMS systems |
The ZCO in-situ analyser measures CO in a cross-stack configuration: transmitter and receiver are mounted on opposite sides of the duct, so the result is the average across the whole section. The eCOMB extractive system measures O₂, CO, CO₂ and temperature and calculates efficiency and excess air, with one panel per emission point.
Flame detection
If the flame goes out while fuel keeps entering the furnace, the accumulated mixture can explode on re-ignition. The flame detector and the burner control unit must shut off the fuel within a defined safety time. Sensor choice depends on the fuel: gas flames emit strongly in the ultraviolet, but the UV component can be screened by water vapour or dust; oil, coal or biomass flames are well detected in the infrared.
LAMTEC F200K and F300K detectors come in UV, IR or UV/IR versions and are SIL 3 certified. The F300K has three operating modes, with different parameters for each fuel, and a safety time adjustable from 1 to 5 s. For gas burners in thermal processing equipment, the Dungs MPA 41xx burner control unit supervises the flame by ionisation and has a second input for an additional detector. On flares, where pilot flame thermocouples fail under thermal shock, the E2T Quasar 2 detects the pilot flame in the infrared from up to 400 m.
CEMS and the European framework
In the EU, emissions from large industrial installations are regulated by Directive 2010/75/EU on industrial emissions (IED), with specific requirements for large combustion plants, while medium combustion plants have their own directive, (EU) 2015/2193. Emission limit values and monitoring obligations for a specific installation are set in its environmental permit, based on the best available techniques (BAT) conclusions. Continuous monitoring must be backed by data quality assurance; the EN 14181 standard defines the levels QAL1 (suitability of the analyser), QAL2 (on-site calibration against the reference method) and QAL3 (ongoing drift checks).
Ascon Tecnologic CEMS systems use QAL1 certified analysers and can measure O₂, CO, NO, NO₂, NOx, SO₂, CO₂, NH₃, total organic carbon, dust and flow. The software calculates averages and validity indices for comparison with legal limits and can include QAL2 and QAL3 check functions. The actual configuration starts from the requirements of the plant’s permit.
The equipment mentioned here, together with burner control units and through-flame imaging systems such as BoilerSpection, which sees through the flame at 3.9 μm, is in our product catalogue.
Frequently asked questions
Can an in-situ O₂ probe replace a CEMS?
No. The probe serves combustion control. Reporting emissions to the authority requires certified analysers, data quality assurance and averaging as specified in the permit.
Why measure CO as well, not just O₂?
Oxygen shows the excess air but not the quality of combustion. CO signals incomplete combustion and lets you lower the O₂ setpoint close to the point where CO starts to rise.
Which flame detector should I choose: UV or IR?
It depends on the fuel and the viewing conditions. UV for gas flames with good visibility, IR for oil, coal or biomass, or when UV is screened. UV/IR detectors cover multi-fuel installations.
Tell us the type of plant, the fuel, the thermal input, the flue gas temperature and the requirements in your permit. We will propose the right analysis, combustion control or flame detection solution and send you an offer through our request a quote page.