KYORITSU KEW 6516 / 6516BT — multifunction installation tester
KYORITSU KEW 6516 / 6516BT multifunction tester: insulation up to 1000 V, loop impedance with Anti-Trip, RCD types AC, A, F, B, earth, continuity, PSC/PFC, SPD; CAT IV 300 V.
| Insulation resistance | 100 / 250 / 500 / 1000 V; up to 2000 MΩ; ±2 % of reading ±6 dgt |
|---|---|
| Loop impedance | 20 / 200 / 2000 Ω (ATT); 2 Ω with 0.001 Ω resolution (25 A); L-N/L-L 20 Ω |
| PSC / PFC | 2000 A / 20 kA; PFC up to 50 kA |
| RCD tests | Type AC, A, F, B (G/S), EV; 6 … 1000 mA; ×½, ×1, ×5, ramp, auto, Uc |
| Earth resistance | 20 / 200 / 2000 Ω; 2-wire and 3-wire methods |
- A quote tailored to your application
- Technical advice on choosing the right model
- Technical support before and after delivery
Description
The KYORITSU KEW 6516 and KEW 6516BT combine in a single instrument the tests required when verifying residential, commercial and industrial electrical installations: insulation resistance, fault loop impedance, residual current devices, earth resistance, continuity, voltage, frequency and phase sequence. They are intended for inspection, preventive maintenance and pre-commissioning checks.
Key benefits
- Anti-Trip (ATT) technology measures the L-PE loop without tripping the RCD, with 3 wires for maximum accuracy or with 2 wires, useful on three-phase circuits without a neutral.
- Loop measurement with 0.001 Ω resolution at a 25 A test current, for measurements close to the transformer, in the main switchboard.
- RCD tests for types AC, A, F, B (general and selective) and EV: ×½, ×1, ×5, ramp, auto and touch voltage.
- The Zs/Ra Limit function automatically checks whether the loop impedance allows the fuse or RCD to trip and displays PASS/FAIL.
- Large color screen, HELP function with the connection diagram for each test, remote-control probe and touch sensor for dangerous voltages on PE.
How to choose the model
KEW 6516 includes all basic functions and data transfer via the supplied 8212-USB USB adapter. KEW 6516BT adds Bluetooth for transferring results to a tablet or smartphone, testing of varistor surge protective devices (SPD) and the PAT function for Class I and II portable appliances. Both can be supplied in a kit with the KEW 8602 adapter for charging stations.
Available models
- KYORITSU KEW 6516 — Multifunction tester with data transfer via the supplied USB adapter.
- KYORITSU KEW 6516BT — Adds Bluetooth, SPD testing and the PAT function; USB adapter optional.
- KYORITSU KEW 6516-EV2 / 6516BT-EV2 — Kits with the KEW 8602 adapter for testing electric vehicle charging stations.
Applications
- Verification of industrial and commercial electrical installations
- Preventive maintenance of electrical panels
- Testing of earthing systems and protective conductors
- Pre-commissioning checks
- Electrical inspection and diagnostics
- Portable appliance testing (PAT)
Technical specifications
| Insulation resistance | 100 / 250 / 500 / 1000 V; up to 2000 MΩ; ±2 % of reading ±6 dgt |
|---|---|
| Loop impedance | 20 / 200 / 2000 Ω (ATT); 2 Ω with 0.001 Ω resolution (25 A); L-N/L-L 20 Ω |
| PSC / PFC | 2000 A / 20 kA; PFC up to 50 kA |
| RCD tests | Type AC, A, F, B (G/S), EV; 6 … 1000 mA; ×½, ×1, ×5, ramp, auto, Uc |
| Earth resistance | 20 / 200 / 2000 Ω; 2-wire and 3-wire methods |
| Continuity | 20 / 200 / 2000 Ω; test current 200 mA or 15 mA |
| Voltage and frequency | 2 … 600 V AC TRMS; 45 … 65 Hz |
| Phase sequence | 48 … 600 V, 45 … 65 Hz |
| SPD (varistor) | 0 … 1049 V, max. 1000 V |
| Display | 3.5″ color LCD |
| Communication | USB (8212-USB adapter); Bluetooth 5.0 on KEW 6516BT |
| Standards and safety | IEC 61010-1 CAT IV 300 V / CAT III 600 V; IEC 61557-1 … 7, 10; IP40 |
| Power supply | 8 AA (LR6) batteries, 1.5 V |
| Dimensions and weight | 136 × 235 × 114 mm; 1350 g with batteries |