KYORITSU KEW 6516 / 6516BT — multifunction installation tester

KYORITSU KEW 6516 / 6516BT multifunction tester: insulation up to 1000 V, loop impedance with Anti-Trip, RCD types AC, A, F, B, earth, continuity, PSC/PFC, SPD; CAT IV 300 V.

Key specifications
Insulation resistance100 / 250 / 500 / 1000 V; up to 2000 MΩ; ±2 % of reading ±6 dgt
Loop impedance20 / 200 / 2000 Ω (ATT); 2 Ω with 0.001 Ω resolution (25 A); L-N/L-L 20 Ω
PSC / PFC2000 A / 20 kA; PFC up to 50 kA
RCD testsType AC, A, F, B (G/S), EV; 6 … 1000 mA; ×½, ×1, ×5, ramp, auto, Uc
Earth resistance20 / 200 / 2000 Ω; 2-wire and 3-wire methods
  • A quote tailored to your application
  • Technical advice on choosing the right model
  • Technical support before and after delivery

Description

The KYORITSU KEW 6516 and KEW 6516BT combine in a single instrument the tests required when verifying residential, commercial and industrial electrical installations: insulation resistance, fault loop impedance, residual current devices, earth resistance, continuity, voltage, frequency and phase sequence. They are intended for inspection, preventive maintenance and pre-commissioning checks.

Key benefits

  • Anti-Trip (ATT) technology measures the L-PE loop without tripping the RCD, with 3 wires for maximum accuracy or with 2 wires, useful on three-phase circuits without a neutral.
  • Loop measurement with 0.001 Ω resolution at a 25 A test current, for measurements close to the transformer, in the main switchboard.
  • RCD tests for types AC, A, F, B (general and selective) and EV: ×½, ×1, ×5, ramp, auto and touch voltage.
  • The Zs/Ra Limit function automatically checks whether the loop impedance allows the fuse or RCD to trip and displays PASS/FAIL.
  • Large color screen, HELP function with the connection diagram for each test, remote-control probe and touch sensor for dangerous voltages on PE.

How to choose the model

KEW 6516 includes all basic functions and data transfer via the supplied 8212-USB USB adapter. KEW 6516BT adds Bluetooth for transferring results to a tablet or smartphone, testing of varistor surge protective devices (SPD) and the PAT function for Class I and II portable appliances. Both can be supplied in a kit with the KEW 8602 adapter for charging stations.

Available models

  • KYORITSU KEW 6516 — Multifunction tester with data transfer via the supplied USB adapter.
  • KYORITSU KEW 6516BT — Adds Bluetooth, SPD testing and the PAT function; USB adapter optional.
  • KYORITSU KEW 6516-EV2 / 6516BT-EV2 — Kits with the KEW 8602 adapter for testing electric vehicle charging stations.

Applications

  • Verification of industrial and commercial electrical installations
  • Preventive maintenance of electrical panels
  • Testing of earthing systems and protective conductors
  • Pre-commissioning checks
  • Electrical inspection and diagnostics
  • Portable appliance testing (PAT)

Technical specifications

Insulation resistance100 / 250 / 500 / 1000 V; up to 2000 MΩ; ±2 % of reading ±6 dgt
Loop impedance20 / 200 / 2000 Ω (ATT); 2 Ω with 0.001 Ω resolution (25 A); L-N/L-L 20 Ω
PSC / PFC2000 A / 20 kA; PFC up to 50 kA
RCD testsType AC, A, F, B (G/S), EV; 6 … 1000 mA; ×½, ×1, ×5, ramp, auto, Uc
Earth resistance20 / 200 / 2000 Ω; 2-wire and 3-wire methods
Continuity20 / 200 / 2000 Ω; test current 200 mA or 15 mA
Voltage and frequency2 … 600 V AC TRMS; 45 … 65 Hz
Phase sequence48 … 600 V, 45 … 65 Hz
SPD (varistor)0 … 1049 V, max. 1000 V
Display3.5″ color LCD
CommunicationUSB (8212-USB adapter); Bluetooth 5.0 on KEW 6516BT
Standards and safetyIEC 61010-1 CAT IV 300 V / CAT III 600 V; IEC 61557-1 … 7, 10; IP40
Power supply8 AA (LR6) batteries, 1.5 V
Dimensions and weight136 × 235 × 114 mm; 1350 g with batteries

Documentation

Quote request

Request a quote for this product

Fill in the form; a TempSystem engineer will reply with a quote and, if needed, with questions about your application.

Requested productKYORITSU KEW 6516 / 6516BT — multifunction installation tester
  1. Send the request (the product is filled in automatically).
  2. We check the application and the right variant.
  3. You receive the technical and commercial offer.

    Drawing, requirements sheet, photo of the measuring point — PDF, Word, Excel, images or ZIP, max. 10 MB.
    Powered by TSync