Skip to content

Dungs MPA 41xx — burner control for gas burners

Manufacturer: DungsDungs MPA

Microprocessor-based burner control for single-stage or modulating gas burners, continuous operation, two flame inputs, SIL3, Profibus DP and optional Modbus.

Key specifications
Rated voltage115 V AC or 230 V AC, −15…+10 %, 50…60 Hz (depending on model)
Power consumptionmax. 10 VA
Fusemax. 6.3 A slow-blow or 10 A fast-acting
OutputsGas valves max. 2 A; fan, ignition, ready signal and fault signal max. 1 A
Flame supervisionIonization (10…20 µA in operation, switch-off threshold 1.2 µA) and gate input for a second detector
  • A quote tailored to your application
  • Technical advice on choosing the right model
  • Technical support before and after delivery

Description

The Dungs MPA 41xx automatically controls single-stage or modulating gas burners, atmospheric or fan-assisted, with or without pilot gas. It is intended in particular for industrial thermal processing equipment compliant with EN 746-2 and allows intermittent or continuous operation.

Key benefits

  • Program sequence and timings (pre-purge, safety time at start-up, post-purge) are set through software parameters, password-protected at service and OEM levels.
  • Two independent flame inputs: ionization and a gate input for a second detector.
  • MPA 4112 and MPA 4122 are configured directly from the display, without a PC; the display shows program status, flame quality and the last 10 faults.
  • Suitable for applications up to SIL3 (IEC 61508, certified by TÜV Süd).
  • Expansion modules for Profibus DP and Modbus, PWM and analog signals.

Versions and accessories

MPA 4111 without display (IP42), MPA 4112 with display (IP54), MPA 4122 with metal housing and display (IP65). Accessories: FLW 10 IR and FLW 20 UV flame detectors, UV 41 / UV 41 HE / UV 42, FLW 41 I ionization module, MPA 41 parameterization and service box, and MPA Vision Box for PC-based setup.

Available models

  • MPA 4111 — Without display, IP42; 230 V AC (259 058) or 115 V AC (259 062).
  • MPA 4112 — With integrated display, IP54; 230 V AC (259 066) or 115 V AC (259 070).
  • MPA 4122 — Metal housing and integrated display, IP65; 230 V AC (260 347) or 115 V AC (260 355).
  • EM2/4, EM2/6 — Expansion modules: Profibus DP, Modbus, shutter; EM2/6 adds PWM and analog inputs/outputs.

Applications

  • Industrial thermal processing equipment (EN 746-2)
  • Atmospheric gas burners
  • Fan-assisted burners, single-stage or modulating
  • Continuous operation

Technical specifications

Rated voltage115 V AC or 230 V AC, −15…+10 %, 50…60 Hz (depending on model)
Power consumptionmax. 10 VA
Fusemax. 6.3 A slow-blow or 10 A fast-acting
OutputsGas valves max. 2 A; fan, ignition, ready signal and fault signal max. 1 A
Flame supervisionIonization (10…20 µA in operation, switch-off threshold 1.2 µA) and gate input for a second detector
Reset after faultButtons and remote reset
Ingress protectionMPA 4111: IP42; MPA 4112: IP54; MPA 4122: IP65
Ambient temperature−40…+70 °C (−20…+60 °C for UL approval)
CommunicationProfibus DP and Modbus via EM2/4 or EM2/6 expansion modules
ApprovalsCE type examination (Gas Appliances Regulation, Pressure Equipment Directive), FM 761, UL 372, UL 1998, CSA C22.2, GOST / Rostechnadzor
Functional safetyUp to SIL3 per IEC 61508 (ed. 2, 2011), certified by TÜV Süd
Application standardEN 746-2

Documentation

Quote request

Request a quote for this product

Fill in the form; a TempSystem engineer will reply with a quote and, if needed, with questions about your application.

Requested productDungs MPA 41xx — burner control for gas burners
  1. Send the request (the product is filled in automatically).
  2. We check the application and the right variant.
  3. You receive the technical and commercial offer.

    Drawing, requirements sheet, photo of the measuring point — PDF, Word, Excel, images or ZIP, max. 10 MB.
    Powered by TSync