Dungs MPA 41xx — burner control for gas burners
Microprocessor-based burner control for single-stage or modulating gas burners, continuous operation, two flame inputs, SIL3, Profibus DP and optional Modbus.
| Rated voltage | 115 V AC or 230 V AC, −15…+10 %, 50…60 Hz (depending on model) |
|---|---|
| Power consumption | max. 10 VA |
| Fuse | max. 6.3 A slow-blow or 10 A fast-acting |
| Outputs | Gas valves max. 2 A; fan, ignition, ready signal and fault signal max. 1 A |
| Flame supervision | Ionization (10…20 µA in operation, switch-off threshold 1.2 µA) and gate input for a second detector |
- A quote tailored to your application
- Technical advice on choosing the right model
- Technical support before and after delivery
Description
The Dungs MPA 41xx automatically controls single-stage or modulating gas burners, atmospheric or fan-assisted, with or without pilot gas. It is intended in particular for industrial thermal processing equipment compliant with EN 746-2 and allows intermittent or continuous operation.
Key benefits
- Program sequence and timings (pre-purge, safety time at start-up, post-purge) are set through software parameters, password-protected at service and OEM levels.
- Two independent flame inputs: ionization and a gate input for a second detector.
- MPA 4112 and MPA 4122 are configured directly from the display, without a PC; the display shows program status, flame quality and the last 10 faults.
- Suitable for applications up to SIL3 (IEC 61508, certified by TÜV Süd).
- Expansion modules for Profibus DP and Modbus, PWM and analog signals.
Versions and accessories
MPA 4111 without display (IP42), MPA 4112 with display (IP54), MPA 4122 with metal housing and display (IP65). Accessories: FLW 10 IR and FLW 20 UV flame detectors, UV 41 / UV 41 HE / UV 42, FLW 41 I ionization module, MPA 41 parameterization and service box, and MPA Vision Box for PC-based setup.
Available models
- MPA 4111 — Without display, IP42; 230 V AC (259 058) or 115 V AC (259 062).
- MPA 4112 — With integrated display, IP54; 230 V AC (259 066) or 115 V AC (259 070).
- MPA 4122 — Metal housing and integrated display, IP65; 230 V AC (260 347) or 115 V AC (260 355).
- EM2/4, EM2/6 — Expansion modules: Profibus DP, Modbus, shutter; EM2/6 adds PWM and analog inputs/outputs.
Applications
- Industrial thermal processing equipment (EN 746-2)
- Atmospheric gas burners
- Fan-assisted burners, single-stage or modulating
- Continuous operation
Technical specifications
| Rated voltage | 115 V AC or 230 V AC, −15…+10 %, 50…60 Hz (depending on model) |
|---|---|
| Power consumption | max. 10 VA |
| Fuse | max. 6.3 A slow-blow or 10 A fast-acting |
| Outputs | Gas valves max. 2 A; fan, ignition, ready signal and fault signal max. 1 A |
| Flame supervision | Ionization (10…20 µA in operation, switch-off threshold 1.2 µA) and gate input for a second detector |
| Reset after fault | Buttons and remote reset |
| Ingress protection | MPA 4111: IP42; MPA 4112: IP54; MPA 4122: IP65 |
| Ambient temperature | −40…+70 °C (−20…+60 °C for UL approval) |
| Communication | Profibus DP and Modbus via EM2/4 or EM2/6 expansion modules |
| Approvals | CE type examination (Gas Appliances Regulation, Pressure Equipment Directive), FM 761, UL 372, UL 1998, CSA C22.2, GOST / Rostechnadzor |
| Functional safety | Up to SIL3 per IEC 61508 (ed. 2, 2011), certified by TÜV Süd |
| Application standard | EN 746-2 |
Documentation